CISA-Published Industrial Control System Vulnerabilities
INEA ME RTU
1. EXECUTIVE SUMMARY
CVSS v3 10.0
ATTENTION: Exploitable remotely/low attack complexity
Vendor: INEA
Equipment: ME RTU
Vulnerability: OS Command Injection
2. RISK EVALUATION
Successful exploitation of this vulnerability could allow remote code execution.
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of ME RTU, a remote terminal unit, are affected:
ME RTU: versions prior to 3.36
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78
Versions of INEA ME RTU firmware prior to 3.36 are vulnerable to operating system (OS) command injection, which could allow an attacker to remotely execute arbitrary code.
CVE-2023-2131 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).
3.3 BACKGROUND
CRITICAL INFRASTRUCTURE SECTORS: Energy, Water and Wastewater, Transportation
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Slovenia
3.4 RESEARCHER
Floris Hendriks of Radboud University reported this vulnerability to CISA.
4. MITIGATIONS
INEA has developed mitigations for this vulnerability and recommends users update to the latest firmware version:
ME RTU: Update to version 3.36 or later.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet.
Locate control system networks and remote devices behind firewalls and isolate them from business networks.
When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.