CISA-Published Industrial Control System Vulnerabilities
SpiderControl SCADAWebServer
1. EXECUTIVE SUMMARY
CVSS v3 4.9
ATTENTION: Exploitable remotely/low attack complexity
Vendor: SpiderControl
Equipment: SCADAWebServer
Vulnerability: Path Traversal
2. RISK EVALUATION
Successful exploitation of this vulnerability could result in a denial-of-service condition
3. TECHNICAL DETAILS
3.1 AFFECTED PRODUCTS
The following versions of SCADAWebServer are affected:
SCADAWebServer: Versions 2.08 and prior
3.2 VULNERABILITY OVERVIEW
3.2.1 IMPROPER LIMITATION OF A PATHNAME TO A RESTRICTED DIRECTORY (‘PATH TRAVERSAL’) CWE-22
SpiderControl SCADA Webserver versions 2.08 and prior are vulnerable to path traversal. An attacker with administrative privileges could overwrite files on the webserver using the HMI’s upload file feature. This could create size zero files anywhere on the webserver, potentially overwriting system files and creating a denial-of-service condition.
CVE-2023-3329 has been assigned to this vulnerability. A CVSS v3 base score of 4.9 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:N/A:H).
3.3 BACKGROUND
CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Commercial Facilities
COUNTRIES/AREAS DEPLOYED: Worldwide (Primarily Europe)
COMPANY HEADQUARTERS LOCATION: Switzerland
3.4 RESEARCHER
Yang Liu from ELEX FEIGONG RESEARCH INSTITUTE of Elex CyberSecurity, Inc. reported this vulnerability to CISA.
4. MITIGATIONS
SpiderControl recommends users update their systems to the latest version.
SpiderControl recommends users apply the following mitigations:
If doing development work on the device, after the development phase is finished, switch off the file upload feature. To do this, go to the file C:wwwZelsWebServ.xml and set the property “file_upload_en” to 0 like so: 0 . This will mitigate the vulnerability in all older versions, and should also be done for the current version in order to prevent unwanted access to the Web-servers html file directory.
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet.
Locate control system networks and remote devices behind firewalls and isolate them from business networks.
When remote access is required, use secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as its connected devices.
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.