Siemens User Management Component

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: User Management Component (UMC)
  • Vulnerability: Heap-based Buffer Overflow

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an unauthenticated remote attacker arbitrary code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports the following products are affected:

  • Opcenter Execution Foundation: All versions
  • Opcenter Intelligence: All versions
  • Opcenter Quality: All versions
  • Opcenter RDL: All versions
  • SIMATIC PCS neo V4.0: All versions
  • SIMATIC PCS neo V4.1: All versions
  • SIMATIC PCS neo V5.0: All versions prior to V5.0 Update 1
  • SINEC NMS: All versions
  • Totally Integrated Automation Portal (TIA Portal) V16: All versions
  • Totally Integrated Automation Portal (TIA Portal) V17: All versions
  • Totally Integrated Automation Portal (TIA Portal) V18: All versions
  • Totally Integrated Automation Portal (TIA Portal) V19: All versions

3.2 Vulnerability Overview

3.2.1 HEAP-BASED BUFFER OVERFLOW CWE-122

Affected products contain a heap-based buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to execute arbitrary code.

CVE-2024-49775 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-49775. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Tenable reported this vulnerability to Siemens.

4. MITIGATIONS

Siemens has released new versions for several affected products and recommends updating to the latest versions. Siemens is preparing further fix versions and recommends countermeasures for products where fixes are not, or are not yet, available.

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • Filter the Ports 4002 and 4004 to only accept connections to/from the IP addresses of machines that run UMC and are part of the UMC network e.g. with an external firewall
  • In addition if no RT server machines are used, Port 4004 can be blocked completely.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-928984 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • December 19, 2024: Initial Publication

Tibbo AggreGate Network Manager

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Tibbo
  • Equipment: AggreGate Network Manager
  • Vulnerability: Unrestricted Upload of File with Dangerous Type

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to achieve code execution on the affected device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Tibbo products are affected:

  • Aggregate Network Manager: Versions 6.34.02 and prior

3.2 Vulnerability Overview

3.2.1 Unrestricted Upload of File with Dangerous Type CWE-434

There is an unrestricted file upload vulnerability where it is possible for an authenticated user (low privileged) to upload an jsp shell and execute code with the privileges of user running the web server.

CVE-2024-12700 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-12700. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Communications, Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Taiwan

3.4 RESEARCHER

Vu Khanh Trinh (@Sonicrr) of VNPT Cyber Immunity working with Trend Micro Zero Day Initiative reported this vulnerability to CISA.

4. MITIGATIONS

Tibbo recommends users update to Versions 6.40.02, 6.34.03, or latest version.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • December 19, 2024: Initial Publication

Schneider Electric Accutech Manager

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 7.5
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Schneider Electric
  • Equipment: Accutech Manager
  • Vulnerability: Classic Buffer Overflow

    2. RISK EVALUATION

Successful exploitation could allow an attacker to cause a crash of the Accutech Manager when receiving a specially crafted request over port 2536/TCP.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Schneider Electric reports that the following products are affected:

  • Schneider Electric Accutech Manager: Versions 2.08.01 and prior

3.2 Vulnerability Overview

3.2.1 BUFFER COPY WITHOUT CHECKING SIZE OF INPUT (‘CLASSIC BUFFER OVERFLOW’) CWE-120

A Classic Buffer Overflow vulnerability exists that could cause a crash of the Accutech Manager when receiving a specially crafted request over port 2536/TCP.

CVE-2024-6918 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy, Water and Wastewater, Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: France

3.4 RESEARCHER

Schneider Electric reported this vulnerability to CISA.

4. MITIGATIONS

Schneider Electric has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • Update Schneider Electric Accutech Manager to version 2.10.0.
  • Instructions are provided with the software installation package on how to verify software revision.

For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document and the associated Schneider Electric Security Notification SEVD-2024-226-01 in PDF and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • December 19, 2024: Initial Publication

Schneider Electric Modicon Controllers

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 5.4
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Schneider Electric
  • Equipment: Modicon Controllers
  • Vulnerability: Cross-site Scripting

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to cause a victim’s browser to run arbitrary JavaScript when visiting a page containing injected payload.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Schneider Electric reports that the following products are affected:

  • Schneider Electric Modicon Controllers M258 / LMC058: All versions
  • Schneider Electric Modicon Controllers M262: Versions prior to 5.2.8.26
  • Schneider Electric Modicon Controllers M251: Versions prior to 5.2.11.24
  • Schneider Electric Modicon Controllers M241: Versions prior to 5.2.11.24

3.2 Vulnerability Overview

3.2.1 IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION (‘CROSS-SITE SCRIPTING’) CWE-79

A Cross-site Scripting  vulnerability exists  where an attacker could cause a victim’s browser run arbitrary JavaScript when they visit a page containing the injected payload.

CVE-2024-6528 has been assigned to this vulnerability. A CVSS v3 base score of 5.4 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:C/C:L/I:L/A:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, and Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: France

3.4 RESEARCHER

Schneider Electric CPCERT reported this vulnerability to CISA.

4. MITIGATIONS

Schneider Electric has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • Schneider Electric Modicon Controllers Version prior to v5.2.11.24: Modicon Controller M241 Firmware version 5.2.11.24 delivered with EcoStruxure Machine Expert v2.2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2.2 of EcoStruxure Machine Expert. Update Modicon Controller M241 to the latest Firmware and perform reboot
  • Schneider Electric Modicon Controllers Version prior to v5.2.11.24: Modicon Controller M251 Firmware version 5.2.11.24 delivered with EcoStruxure Machine Expert v2.2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application. https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2.2 of EcoStruxure Machine Expert. Update Modicon Controller M251 to the latest Firmware and perform reboot
  • Schneider Electric Modicon Controllers M262 Versions prior to v5.2.8.26: Modicon Controller M262 Firmware version 5.2.8.26 delivered with EcoStruxure Machine Expert v2.2.2 includes a fix for this vulnerability and can be updated through the Schneider Electric Software Update (SESU) application.https://www.se.com/ww/en/product-range/2226-ecostruxure-machine-expert-software/ On the engineering workstation, update to v2.2.2 of EcoStruxure Machine Expert. Update Modicon Controller M262 to the latest Firmware and perform reboot
  • Schneider Electric Modicon Controllers Version prior to v5.2.11.24, Schneider Electric Modicon Controllers M258 / LMC058 All versions , Schneider Electric Modicon Controllers M262 Versions prior to v5.2.8.26, Schneider Electric Modicon Controllers Version prior to v5.2.11.24: Users should immediately apply the following mitigations to reduce the risk of exploit: Use controllers and devices only in a protected environment to minimize network exposure and ensure that they are not accessible from public internet or untrusted networks. Ensure usage of user management and password features. User rights are enabled by default and forced to create a strong password at first use. Deactivate the Webserver after use when not needed. Use encrypted communication links. Setup network segmentation and implement a firewall to block all unauthorized access to port 80/HTTP and 443/HTTPS. Use VPN (Virtual Private Networks) tunnels if remote access is required. The “Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment” provide product specific chapters to ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric’s security notification service here

For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document and the associated Schneider Electric Security Notification SEVD-2024-191-04 in PDF and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • December 19, 2024: Initial Publication

Beckhoff Automation TwinCAT Package Manager

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.0
  • ATTENTION: Low Attack Complexity
  • Vendor: Beckhoff Automation
  • Equipment: TwinCAT Package Manager
  • Vulnerability: Improper Neutralization of Special Elements used in an OS Command (‘OS Command Injection’)

2. RISK EVALUATION

Successful exploitation this vulnerability could allow a local attacker with administrative access rights to execute arbitrary OS commands on the affected system.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Beckhoff Automation products are affected:

  • TwinCAT Package Manager: Versions prior to 1.0.603.0

3.2 Vulnerability Overview

3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78

A local user with administrative access rights can enter specially crafted values for settings at the user interface (UI) of the TwinCAT Package Manager which then causes arbitrary OS commands to be executed.

CVE-2024-8934 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:H/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-8934. A base score of 7.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:H/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N)

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

elcazator of Elex Feigong Research Institute of Elex CyberSecurity, Inc. reported this vulnerability to CISA.

4. MITIGATIONS

Beckhoff Automation recommends users update to at least version 1.0.613.0.

Additionally, Beckhoff Automation has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • Administrative users should always act thoroughly and inspect the values which they enter.
  • Please update to a recent version of the affected product.

For more information CERT@VDE has released security advisory VDE-2024-064

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.

5. UPDATE HISTORY

  • November 7, 2024: Initial Publication

Bosch Rexroth IndraDrive

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Bosch Rexroth
  • Equipment: IndraDrive
  • Vulnerability: Uncontrolled Resource Consumption

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service, rendering the device unresponsive by sending arbitrary UDP messages.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Bosch Rexroth reports that the following versions of IndraDrive, servo drive system, are affected:

  • Bosch Rexroth AG IndraDrive FWA-INDRV*MP*: 17VRS < 20V36

3.2 Vulnerability Overview

3.2.1 Uncontrolled Resource Consumption CWE-400

A vulnerability in the PROFINET stack implementation of the IndraDrive of Bosch Rexroth allows an attacker to cause a denial-of-service, rendering the device unresponsive by sending arbitrary UDP messages.

CVE-2024-48989 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2024-48989. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Roni Gavrilov from OTORIO reported this vulnerability to CISA.

4. MITIGATIONS

Bosch Rexroth has fixed this vulnerability starting with FWA-INDRV-MP-20V36. Bosch Rexroth recommends updating as soon as possible.

In use cases in which a device update is not possible or not feasible, Bosch Rexroth recommends compensatory measures which prevent or at least complicate taking advantage of the vulnerability. Always define such compensatory measures individually, in the context of the operational environment.

Some possible measures are described in “Security Manual Electric Drives and Controls”, like network segmentation. In general, it is highly recommended to implement the measures described in “Security Manual Drives and Controls”.

For more information, refer to the Bosch PSIRT Security Advisory BOSCH-SA-2584444

Please contact the Bosch PSIRT if you have feedback, comments, or additional information about this vulnerability at: psirt@bosch.com .

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • November 7, 2024: Initial Publication

Delta Electronics DIAScreen

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.4
  • ATTENTION: Low attack complexity
  • Vendor: Delta Electronics
  • Equipment: DIAScreen
  • Vulnerabilities: Stack-based Buffer Overflow

2. RISK EVALUATION

Successful exploitation of this these vulnerabilities could crash the device being accessed; a buffer overflow condition may allow remote code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of DIAScreen, which is a component of Delta’s DIAStudio Smart Machine Suite integrated engineering software package, are affected:

  • DIAScreen: versions prior to v1.5.0

3.2 Vulnerability Overview

3.2.1 Stack-based Buffer Overflow CWE-121

If an attacker tricks a valid user into running Delta Electronics DIAScreen with a file containing malicious code, a stack-based buffer overflow in BACnetObjectInfo can be exploited, allowing the attacker to remotely execute arbitrary code.

CVE-2024-47131 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-47131. A base score of 8.4 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 Stack-based Buffer Overflow CWE-121

If an attacker tricks a valid user into running Delta Electronics DIAScreen with a file containing malicious code, a stack-based buffer overflow in BACnetParameter can be exploited, allowing the attacker to remotely execute arbitrary code.

CVE-2024-39605 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-39605. A base score of 8.4 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.3 Stack-based Buffer Overflow CWE-121

If an attacker tricks a valid user into running Delta Electronics DIAScreen with a file containing malicious code, a stack-based buffer overflow in CEtherIPTagItem can be exploited, allowing the attacker to remotely execute arbitrary code.

CVE-2024-39354 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-39354. A base score of 8.4 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Taiwan

3.4 RESEARCHER

Natnael Samson working with Trend Micro Zero Day Initiative reported these vulnerabilities to CISA.

4. MITIGATIONS

Delta Electronics has released v1.5.0 of DIAScreen (login required) and recommends users install this update on all affected systems.

For more information, please see the Delta product cybersecurity advisory for these issues.

CISA recommends users take the following measures to protect themselves from social engineering attacks:

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.

5. UPDATE HISTORY

  • November 7, 2024: Initial Publication

Rockwell Automation FactoryTalk ThinManager

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: FactoryTalk ThinManager
  • Vulnerabilities: Missing Authentication For Critical Function, Out-of-Bounds Read

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to send crafted messages to the device resulting in database manipulation or a denial-of-service condition.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Rockwell Automation FactoryTalk product versions are affected:

  • ThinManager: Versions 11.2.0 to 11.2.9
  • ThinManager: Versions 12.0.0 to 12.0.7
  • ThinManager: Versions 12.1.0 to 12.1.8
  • ThinManager: Versions 13.0.0 to 13.0.5
  • ThinManager: Versions 13.1.0 to 13.1.3
  • ThinManager: Versions 13.2.0 to 13.2.2
  • ThinManager: Version 14.0.0

3.2 Vulnerability Overview

3.2.1 MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306

An authentication vulnerability exists in the affected product. The vulnerability could allow a threat actor with network access to send crafted messages to the device, potentially resulting in database manipulation.

CVE-2024-10386 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-10386. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 OUT-OF-BOUNDS READ CWE-125

A denial-of-service vulnerability exists in the affected product. The vulnerability could allow a threat actor with network access to send crafted messages to the device, resulting in a denial-of-service condition.

CVE-2024-10387 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2024-10387. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Tenable Network Security reported these vulnerabilities to Rockwell Automation.

4. MITIGATIONS

Rockwell Automation has provided a fix for the affected versions on the FactoryTalk ThinManager download site.

Rockwell Automation encourages users of the affected software to apply these risk mitigations if possible.

  • Implement network hardening for ThinManager Device(s) by limiting communications to TCP 2031 to only the devices that need connection to the ThinManager.
  • For information on how to mitigate security risks on industrial automation control systems, users are encouraged to implement Rockwell Automation’s suggested security best practices to minimize the risk of the vulnerability.

For more information, see Rockwell Automation’s security bulletin.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 31, 2024: Initial Publication

Delta Electronics InfraSuite Device Master

View CSAF

1. EXECUTIVE SUMMARY

CVSS v4 9.3
ATTENTION: Exploitable remotely/low attack complexity
Vendor: Delta Electronics
Equipment: InfraSuite Device Master
Vulnerability: Deserialization of Untrusted Data

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an unauthenticated attacker to remotely execute arbitrary code.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of InfraSuite Device Master, a real-time device monitoring software, are affected:

InfraSuite Device Master: Versions 1.0.12 and prior

3.2 Vulnerability Overview

3.2.1 DESERIALIZATION OF UNTRUSTED DATA CWE-502

Delta Electronics InfraSuite Device Master versions prior to 1.0.12 are affected by a deserialization vulnerability that targets the Device-Gateway, which could allow deserialization of arbitrary .NET objects prior to authentication, resulting in remote code execution.

CVE-2024-10456 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-10456. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Taiwan

3.4 RESEARCHER

Simon Humbert of Trend Micro reported this vulnerability to CISA.

4. MITIGATIONS

Delta Electronics states that this issue was fixed by version 1.0.13 released in October 2024. Delta recommends updating to version 1.0.13 or later.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

Do not click web links or open attachments in unsolicited email messages.
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

October 29, 2024: Initial Publication

Siemens InterMesh Subscriber Devices

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

CVSS v4 10.0
ATTENTION: Exploitable remotely/low attack complexity
Vendor: Siemens
Equipment: InterMesh
Vulnerabilities: OS Command Injection, Missing Authentication for Critical Function, Execution with Unnecessary Privileges, Incorrect Privilege Assignment

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to perform remote code execution, execute commands, write arbitrary files, or execute arbitrary commands.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Siemens InterMesh Subscriber Devices, a wireless alarm reporting system, are affected:

InterMesh 7177 Hybrid 2.0 Subscriber: All versions prior to V8.2.12
InterMesh 7707 Fire Subscriber: All versions prior to V7.2.12

3.2 Vulnerability Overview

3.2.1 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78

The web server of affected devices does not sanitize the input parameters in specific GET requests that allow for code execution on operating system level. In combination with other vulnerabilities (CVE-2024-47902, CVE-2024-47903, CVE-2024-47904) this could allow an unauthenticated remote attacker to execute arbitrary code with root privileges.

CVE-2024-47901 has been assigned to this vulnerability. A CVSS v3.1 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-47901. A base score of 10.0 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H).

3.2.2 MISSING AUTHENTICATION FOR CRITICAL FUNCTION CWE-306

The web server of affected devices does not authenticate GET requests that execute specific commands (such as ping) on operating system level.

CVE-2024-47902 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:L/A:N).

A CVSS v4 score has also been calculated for CVE-2024-47902. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:N/SC:L/SI:L/SA:N).

3.2.3 EXECUTION WITH UNNECESSARY PRIVILEGES CWE-250

The web server of affected devices allows to write arbitrary files to the web server’s DocumentRoot directory.

CVE-2024-47903 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:L/A:N).

A CVSS v4 score has also been calculated for CVE-2024-47903. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:L/VA:N/SC:N/SI:L/SA:N).

3.2.4 INCORRECT PRIVILEGE ASSIGNMENT CWE-266

The affected devices contain a SUID binary that could allow an authenticated local attacker to execute arbitrary commands with root privileges.

CVE-2024-47904 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-47904. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
COUNTRIES/AREAS DEPLOYED: Worldwide
COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

AES Corporation and Jean Pereira from CYTRES reported these vulnerabilities to Siemens. Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

InterMesh 7177 Hybrid 2.0 Subscriber: Update to V8.2.12 or later version
InterMesh 7707 Fire Subscriber: Update to V7.2.12 or later version
Restrict access to the InterMesh network to trusted systems and persons only

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-333468 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
Locate control system networks and remote devices behind firewalls and isolating them from business networks.
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

October 29, 2024: Initial Publication