Schneider Electric EcoStruxure

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.5
  • ATTENTION: Low attack complexity
  • Vendor: Schneider Electric
  • Equipment: EcoStruxure
  • Vulnerability: Uncontrolled Search Path Element

2. RISK EVALUATION

Successful exploitation of this vulnerability allows for local privilege escalation, which could lead to the execution of a malicious Dynamic-Link Library (DLL).

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Schneider Electric EcoStruxure products and versions, which incorporate Revenera FlexNet Publisher, are affected:

  • EcoStruxure Control Expert: Versions prior to V16.1
  • EcoStruxure Process Expert: All versions
  • EcoStruxure OPC UA Server Expert: All versions
  • EcoStruxure Control Expert Asset Link: Versions prior to V4.0 SP1
  • EcoStruxure Machine SCADA Expert Asset Link: All versions
  • EcoStruxure Architecture Builder: Versions prior to V7.0.18
  • EcoStruxure Operator Terminal Expert: All versions
  • Vijeo Designer: Version prior to V6.3SP1 HF1
  • EcoStruxure Machine Expert including EcoStruxure Machine Expert Safety: All versions
  • EcoStruxure Machine Expert Twin: All versions
  • Zelio Soft 2: All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 Uncontrolled Search Path Element CWE-427

A misconfiguration in lmadmin.exe of FlexNet Publisher versions prior to 2024 R1 (11.19.6.0) allows the OpenSSL configuration file to load from a non-existent directory. An unauthorized, locally authenticated user with low privileges can potentially create the directory and load a specially crafted openssl.conf file leading to the execution of a malicious DLL (Dynamic-Link Library) with elevated privileges.

CVE-2024-2658 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-2658. A base score of 8.5 has been calculated; the CVSS vector string is (AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Energy, Food and Agriculture, Government Services and Facilities, Transportation Systems, Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: France

3.4 RESEARCHER

Xavier DANEST of Trend Micro Zero Day Initiative reported this vulnerability to Revenera PSIRT.

4. MITIGATIONS

Schneider Electric recommends that users of the following products follow these actions:

  • EcoStruxure Control Expert: Versions prior to V16.1 – Version V16.1 of EcoStruxure Control Expert includes a fix for this vulnerability and is available for download here. Reboot the computer after installation is completed.
  • EcoStruxure Architecture Builder: Versions prior to V7.0.18 – Version V7.0.18 of EcoStruxure Architecture Builder includes a fix for this vulnerability and is available for download here.
  • EcoStruxure Control Expert Asset Link: Versions prior to V4.0 SP1 – Version V4.0SP1 of EcoStruxure Control Expert Asset Link includes a fix for this vulnerability and is available for download here.
  • Vijeo Designer: Version prior to V6.3SP1 HF1 – Version V6.3SP1 HF1 of Vijeo Designer includes a fix for this vulnerability. Please contact your Schneider Electric Customer Support to get Vijeo Designer version V6.3SP1 HF1 software.

Users should follow appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or an offline infrastructure. Contact Schneider Electric’s Customer Care Center if you need assistance removing a patch.

If users choose not to apply the remediation provided above, they should immediately apply the following mitigations in order to reduce the risk of exploit:

Schneider Electric is establishing a remediation plan for all future versions of the following that will include a fix for this vulnerability:

  • EcoStruxure Process Expert
  • EcoStruxure OPC UA Server Expert
  • EcoStruxure Machine SCADA Expert – Asset Link
  • EcoStruxure Operator Terminal Expert
  • EcoStruxure Machine Expert including
  • EcoStruxure Machine Expert Safety
  • EcoStruxure Machine Expert Twin
  • Zelio Soft 2

We will update this document when the remediation is available. Until then, users should immediately apply the following mitigations to reduce the risk of exploit:

  • Limit authenticated user access to the workstation and implement existing User Account Control practices.
  • Follow workstation, network and site-hardening guidelines in the Recommended Cybersecurity Best Practices guide available for download here.

To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric’s security notification service here.

General Security Recommendations

Schneider Electric strongly recommends the following industry cybersecurity best practices:

  • Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
  • Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
  • Place all controllers in locked cabinets and never leave them in the “Program” mode.
  • Never connect programming software to any network other than the network intended for that device.
  • Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
  • Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
  • Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.

For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.
    CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.

5. UPDATE HISTORY

  • February 6, 2025: Initial Publication

Trimble Cityworks

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.6
  • ATTENTION: Exploitable remotely/low attack complexity/known public exploitation
  • Vendor: Trimble
  • Equipment: Cityworks
  • Vulnerability: Deserialization of Untrusted Data

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an authenticated user to perform a remote code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Trimble Cityworks, an asset and work management system, are affected:

  • Cityworks: All versions prior to 23.10

3.2 VULNERABILITY OVERVIEW

3.2.1 DESERIALIZATION OF UNTRUSTED DATA CWE-502

Trimble Cityworks versions prior to 23.10 are vulnerable to a deserialization vulnerability. This could allow an authenticated user to perform a remote code execution attack against a customer’s Microsoft Internet Information Services (IIS) web server.

CVE-2025-0994 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-0994. A base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Trimble reported this vulnerability to CISA.

4. MITIGATIONS

Cityworks has released the following update guidance for users:

  • Trimble will be releasing updated versions to both 15.x (15.8.9 available January 28, 2025) and Cityworks 23.x software releases (23.10 available January 29, 2025). Information on the updated versions will be available through the normal channels via the Cityworks Support Portal(Login required). On-premises users should install the updated version immediately. These updates will be automatically applied to all Cityworks Online (CWOL) deployments.
  • Trimble has observed that some on-premises deployments may have overprivileged Internet Information Services (IIS) identity permissions. For avoidance of doubt, and in accordance with Trimble’s technical documentation, IIS should not be run with local or domain level administrative privileges on any site. Please refer to the direction in the latest release notes in the Cityworks Support Portal(Login required) for more information on how to update IIS identity permissions. Trimble’s CWOL customers have their IIS identity permissions set appropriately and do not need to take this action.
  • Trimble has observed that some deployments have inappropriate attachment directory configurations. Trimble recommends that attachment directory root configuration should be limited to folders/subfolders which only contain attachments. Please refer to the direction in the latest release notes in the Cityworks Support Portal(Login required) for more information on how to ensure proper configuration of the attachment directory.

For more information, see Trimble’s notification.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

CISA has received reports of this vulnerability being actively exploited.

5. UPDATE HISTORY

  • February 06, 2025: Initial Publication

Schneider Electric Web Designer for Modicon

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 7.8
  • ATTENTION: Low attack complexity
  • Vendor: Schneider Electric
  • Equipment: Web Designer for Modicon
  • Vulnerability: Improper Restriction of XML External Entity Reference

2. RISK EVALUATION

Successful exploitation of this vulnerability could result in information disclosure, workstation integrity and potential remote code execution on the compromised computer.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Web Designer for Modicon are affected:

  • Web Designer for BMXNOR0200H: All versions
  • Web Designer for BMXNOE0110(H): All versions
  • Web Designer for BMENOC0311(C): All versions
  • Web Designer for BMENOC0321(C): All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER RESTRICTION OF XML EXTERNAL ENTITY REFERENCE CWE-611

The affected product is vulnerable to an improper restriction of XML external entity reference vulnerability that could cause information disclosure, impacts to workstation integrity, and potential remote code execution on the compromised computer when a specifically crafted XML file is imported in the Web Designer configuration tool.

CVE-2024-12476 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Energy, Food and Agriculture, Government Facilities, Transportation Systems, Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: France

3.4 RESEARCHER

Jin Huang of ADLab of Venustech reported this vulnerability Schneider Electric.

4. MITIGATIONS

Web Designer tool project file is based on XML language with specific parameters. To ensure the integrity of this file please follow the recommendations below:

  • Encrypt project file (XML configuration file) when stored and restrict the access to only trusted users.
  • When exchanging files over the network, use secure communication protocols.
  • Only open project files received from a trusted source.
  • Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage.

To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric’s security notification service here: https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp

Schneider Electric strongly recommends the following industry cybersecurity best practices.

  • Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
  • Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
  • Place all controllers in locked cabinets and never leave them in the “Program” mode.
  • Never connect programming software to any network other than the network intended for that device.
  • Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
  • Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
  • Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have their own vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.

For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.

For more information, see Schneider Electric security notification “SEVD-2025-014-04 Web Server on Modicon M340 and BMXNOE0100/0110, BMXNOR0200H communication modules”

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.

5. UPDATE HISTORY

  • February 4, 2025: Initial Publication

Elber Communications Equipment

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity/public exploits are available
  • Vendor: Elber
  • Equipment: Communications Equipment
  • Vulnerabilities: Authentication Bypass Using an Alternate Path or Channel, Hidden Functionality

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker unauthorized administrative access to the affected device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Elber Communications Equipment are affected:

  • Signum DVB-S/S2 IRD: Versions 1.999 and prior
  • Cleber/3 Broadcast Multi-Purpose Platform: Version 1.0
  • Reble610 M/ODU XPIC IP-ASI-SDH: Version 0.01
  • ESE DVB-S/S2 Satellite Receiver: Versions 1.5.179 and prior
  • Wayber Analog/Digital Audio STL: Version 4

3.2 VULNERABILITY OVERVIEW

3.2.1 Authentication Bypass Using an Alternate Path or Channel CWE-288

Multiple Elber products are affected by an authentication bypass vulnerability which allows unauthorized access to the password management functionality. Attackers can exploit this issue by manipulating the endpoint to overwrite any user’s password within the system. This grants them unauthorized administrative access to protected areas of the application, compromising the device’s system security.

CVE-2025-0674 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-0674. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.2 Hidden Functionality CWE-912

Multiple Elber products suffer from an unauthenticated device configuration and client-side hidden functionality disclosure.

CVE-2025-0675 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2025-0675. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Communications
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Italy

3.4 RESEARCHER

Gjoko Krstic of Zero Science Lab reported these vulnerabilities to CISA.

4. MITIGATIONS

Elber does not plan to mitigate these vulnerabilities because this equipment is either end of life or almost end of life. Users of affected versions of Elber Signum DVB-S/S2 IRD, Cleber/3 Broadcast Multi-Purpose Platform, Reble610 M/ODU XPIC IP-ASI-SDH, ESE DVB-S/S2 Satellite Receiver, and Wayber Analog/Digital Audio STL are invited to contact Elber customer support for additional information.

CISA recommends users take defensive measures to minimize the risk of exploitation of this these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 4, 2025: Initial Publication

Schneider Electric Modicon M340 and BMXNOE0100/0110, BMXNOR0200H

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 8.6
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Schneider Electric
  • Equipment: Modicon M340 and BMXNOE0100/0110, BMXNOR0200H
  • Vulnerability: Exposure of Sensitive Information to an Unauthorized Actor

2. RISK EVALUATION

Successful exploitation of this vulnerability could cause information disclosure of a restricted web page, modification of a web page, and a denial of service when specific web pages are modified and restricted functions invoked.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Schneider Electric products, Modicon M340 and BMXNOE0100/0110, BMXNOR0200H, are affected:

  • Modicon M340 processors (part numbers BMXP34*): All versions
  • BMXNOE0100: All versions
  • BMXNOE0110: All versions
  • BMXNOR0200H: Versions prior to SV1.70IR26

3.2 VULNERABILITY OVERVIEW

3.2.1 EXPOSURE OF SENSITIVE INFORMATION TO AN UNAUTHORIZED ACTOR CWE-200

The affected products are vulnerable to an exposure of sensitive information to an unauthorized actor vulnerability, which could cause information disclosure of restricted web page, modification of web page, and denial of service when specific web pages are modified and restricted functions invoked.

CVE-2024-12142 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Energy
  • COUNTRIES/AREAS DEPLOYED: France
  • COMPANY HEADQUARTERS LOCATION: Worldwide

3.4 RESEARCHER

Schneider Electric reported this vulnerability to CISA.

4. MITIGATIONS

Schneider Electric has identified the following specific workarounds and mitigations users can apply to reduce risk:

BMXNOR0200H: Version SV1.70IR26 of BMXNOR0200H includes a fix for this vulnerability and is available for download.

Users should use appropriate patching methodologies when applying these patches to their systems. Schneider Electric strongly recommends the use of back-ups and evaluating the impact of these patches in a testing and development environment, or on an offline infrastructure. Contact Schneider Electric’s Customer Care Center for assistance removing a patch.

Schneider Electric is establishing a remediation plan for all future versions of Modicon M340 processors BMXP34*, BMXNOE0100 and BMXNOE0110 that will include a fix for this vulnerability. They will provide an update when the remediation is available. Until then, users should immediately apply the following mitigations to reduce the risk of exploit:

  • Set up network segmentation and implement a firewall to block all unauthorized access to FTP Port 21/TCP on the devices.
  • Disable FTP service via EcoStruxureTM Control Expert. This is disabled by default when a new application is created.
  • Disable Web server service via EcoStruxureTM Control Expert. This is disabled by default when a new application is created.
  • Configure the Access Control List following the recommendation on the “Modicon Controllers System Cybersecurity”

Schneider Electric strongly recommends the following industry cybersecurity best practices.

  • Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
  • Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
  • Place all controllers in locked cabinets and never leave them in the “Program” mode.
  • Never connect programming software to any network other than the network intended for that device.
  • Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
  • Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
  • Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
  • When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.

For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.

For more information, see Schneider Electric security notification “SEVD-2025-014-05 Web Server on Modicon M340 and BMXNOE0100/0110, BMXNOR0200H communication modules”

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 4, 2025: Initial Publication

AutomationDirect C-more EA9 HMI

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: AutomationDirect
  • Equipment: C-more EA9 HMI
  • Vulnerability: Buffer Copy without Checking Size of Input (‘Classic Buffer Overflow’)

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service condition or achieve remote code execution on the affected device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Automation Direct products are affected:

  • C-more EA9 HMI EA9-T6CL: v6.79 and prior
  • C-more EA9 HMI EA9-T7CL-R: v6.79 and prior
  • C-more EA9 HMI EA9-T7CL: v6.79 and prior
  • C-more EA9 HMI EA9-T8CL: v6.79 and prior
  • C-more EA9 HMI EA9-T10CL: v6.79 and prior
  • C-more EA9 HMI EA9-T10WCL: v6.79 and prior
  • C-more EA9 HMI EA9-T12CL: v6.79 and prior
  • C-more EA9 HMI EA9-T15CL-R: v6.79 and prior
  • C-more EA9 HMI EA9-T15CL: v6.79 and prior
  • C-more EA9 HMI EA9-RHMI: v6.79 and prior

3.2 VULNERABILITY OVERVIEW

3.2.1 Buffer Copy without Checking Size of Input (‘Classic Buffer Overflow’) CWE-120

AutomationDirect C-more EA9 HMI contains a function with bounds checks that can be skipped, which could result in an attacker abusing the function to cause a denial-of-service condition or achieving remote code execution on the affected device.

CVE-2025-0960 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-0960. A base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Sharon Brizinov of Claroty Team82 reported this vulnerability to CISA.

4. MITIGATIONS

AutomationDirect recommends that users update C-MORE EA9 HMI software and firmware to V6.80.

If an immediate update is not feasible, AutomationDirect recommends considering the following interim steps until the programming software can be updated:

  • Isolate the HMI Workstation: Disconnect the HMI from external networks (e.g., internet or corporate LAN) to limit exposure to external threats.
  • Use dedicated, secure internal networks or air-gapped systems for communication with programmable devices.
  • Control Access: Restrict physical and logical access to the HMI to authorized personnel only.
  • Implement Whitelisting: Use application whitelisting to allow only pre-approved and trusted software to execute on the HMI. Block untrusted or unauthorized applications.
  • Apply Endpoint Security Measures: Use antivirus or endpoint detection and response (EDR) tools to monitor for and mitigate threats. Ensure that host-based firewalls are properly configured to block unauthorized access.
  • Monitor and Log Activity: Enable logging and monitoring of system activities to detect potential anomalies or unauthorized actions. Regularly review logs for suspicious activity.
  • Use Secure Backup and Recovery: Regularly back up the workstation and its configurations to a secure location. Test recovery procedures to ensure minimal downtime in the event of an incident.
  • Conduct Regular Risk Assessments: Continuously assess the risks posed by the outdated software and adjust mitigation measures as necessary.

For more information, please see the AutomationDirect security advisory.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 4, 2025: Initial Publication

Schneider Electric Pro-face GP-Pro EX and Remote HMI

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 6.1
  • ATTENTION: Exploitable remotely
  • Vendor: Schneider Electric
  • Equipment: Pro-face GP-Pro EX and Remote HMI
  • Vulnerability: Improper Enforcement of Message Integrity During Transmission in a Communication Channel

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow man-in-the-middle attacks, resulting in information disclosure, integrity issues, and operational failures.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Pro-face GP-Pro EX and Remote HMI are affected:

  • Pro-face GP-Pro EX: All versions
  • Pro-face Remote HMI: All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER ENFORCEMENT OF MESSAGE INTEGRITY DURING TRANSMISSION IN A COMMUNICATION CHANNEL CWE-924

The affected products are vulnerable to an improper enforcement of message integrity during transmission in a communication channel vulnerability that could cause partial loss of confidentiality, loss of integrity, and availability of the HMI when attacker performs man-in-the-middle attack by intercepting the communication.

CVE-2024-12399 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.1 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:R/S:U/C:L/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2024-12399. A base score of 6.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:H/AT:N/PR:N/UI:P/VC:L/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: France

3.4 RESEARCHER

Haichuan Xu from the Georgia Institute of Technology reported this vulnerability to Schneider Electric.

4. MITIGATIONS

Schneider Electric is establishing a remediation plan for all future versions of Pro-face GP-Pro EX and Pro-face Remote HMI that will include a fix for this vulnerability. Schneider Electric will provide an update when the remediation is available. Until then, users should immediately apply the following mitigations to reduce the risk of exploit:

For users requiring the use of Pro-face Remote HMI, Schneider Electric recommends using following mitigations:

For users not using the Pro-face Remote HMI, Schneider Electric recommends using following mitigations to reduce the risk of exploit:

  • Disabling the Pro-face Remote HMI feature (deactivated by default). For more details refer to the GP-Pro EX V4.0 Reference Manual section “Pro-face Remote HMI Settings.”

Schneider Electric strongly recommends the following industry cybersecurity best practices.

  • Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
  • Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
  • Place all controllers in locked cabinets and never leave them in the “Program” mode.
  • Never connect programming software to any network other than the network intended for that device.
  • Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
  • Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
  • Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
  • When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.

For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.

For more information, see Schneider Electric security notification “SEVD-2025-014-02 Schneider Electric Security Notification Pro-face GP-Pro EX and Remote HMI”

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 4, 2025: Initial Publication

Schneider Electric Modicon M580 PLCs, BMENOR2200H and EVLink Pro AC

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Schneider Electric
  • Equipment: Modicon M580 PLCs, BMENOR2200H and EVLink Pro AC
  • Vulnerability: Incorrect Calculation of Buffer Size

2. RISK EVALUATION

Successful exploitation of this vulnerability could cause a denial-of-service of the product when an unauthenticated user sends a crafted HTTPS packet to the webserver.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Modicon M580 PLCs, BMENOR2200H and EVLink Pro AC are affected:

  • Modicon M580 CPU (part numbers BMEP* and BMEH*, excluding M580 CPU Safety): Versions prior to SV4.30
  • Modicon M580 CPU Safety (part numbers BMEP58-S and BMEH58-S): Versions prior to SV4.21
  • BMENOR2200H: All versions
  • EVLink Pro AC: Versions prior to v1.3.10

3.2 VULNERABILITY OVERVIEW

3.2.1 INCORRECT CALCULATION OF BUFFER SIZE CWE-131

The affected product is vulnerable to an incorrect calculation of buffer size vulnerability which could cause a denial-of-service of the product when an unauthenticated user is sending a crafted HTTPS packet to the webserver.

CVE-2024-11425 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2024-11425. A base score of 8.7 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities, Critical Manufacturing, Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: France

3.4 RESEARCHER

Schneider Electric reported this vulnerability to CISA.

4. MITIGATIONS

Schneider Electric has identified the following remediations users can apply to reduce risk:

  • Modicon M580 CPU (partnumbers BMEP* and BMEH*,excluding M580 CPU Safety): Version SV4.30 of Modicon M580 firmware includes a fix for this vulnerability and is available for download.
  • Modicon M580 CPU Safety part numbers BMEP58-S and MEH58-S): Version SV4.21 of Modicon M580 firmware includes a fix for this vulnerability and is available for download.
  • EVLink Pro AC: Version V1.3.10 of EVLink Pro AC firmware includes a fix for this vulnerability and is available here.

Users should use appropriate patching methodologies when applying these patches to their systems. Schneider Electric strongly recommends making use of back-ups and evaluating the impact of these patches in a testing and development environment or on an offline infrastructure. Contact Schneider Electric’s Customer Care Center if assistance is needed for removing a patch.

If users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:

  • Modicon M580 CPU (partnumbers BMEP* and BMEH*,excluding M580 CPU Safety): Set up network segmentation and implement a firewall to block all unauthorized access to Port 443/TCP. Configure the access control list following the recommendations of the user manuals: “Modicon M580, Hardware, Reference Manual”
  • Modicon M580 CPU Safety part numbers BMEP58-S and MEH58-S): Set up network segmentation and implement a firewall to block all unauthorized access to Port 443/TCP. Configure the access control list following the recommendations of the user manuals: “Modicon M580, Hardware, Reference Manual”
  • BMENOR2200H: Schneider Electric is establishing a remediation plan for BMENOR2200H that will include a fix for CVE-2024-11425. They will update SEVD-2025-014-01 when the remediation is available. Until then, users should immediately set up network segmentation and implement a firewall to block all unauthorized access to Port 443/TCP.
  • EVLink Pro AC: Follow the EVlink Pro AC cybersecurity guide

Schneider Electric strongly recommends the following industry cybersecurity best practices.

  • Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
  • Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
  • Place all controllers in locked cabinets and never leave them in the “Program” mode.
  • Never connect programming software to any network other than the network intended for that device.
  • Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
  • Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
  • Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
  • When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.

For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.

For more information, see Schneider Electric security notification “SEVD-2025-014-01 Modicon M580 PLCs, BMENOR2200H and EVLink Pro AC”

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 4, 2025: Initial Publication

Rockwell Automation 1756-L8zS3 and 1756-L3 and 1756-L3

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.1
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Rockwell Automation
  • Equipment: 1756-L8zS3, 1756-L3zS3
  • Vulnerability: Improper Handling of Exceptional Conditions

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow a remote, non-privileged user to send malicious requests resulting in a major nonrecoverable fault causing a denial-of-service condition.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Rockwell Automation products are affected:

  • 1756-L8zS3: Versions prior to V33.017, V34.014, V35.013, V36.011
  • 1756-L3zS3: Versions prior to V33.017, V34.014, V35.013, V36.011

3.2 VULNERABILITY OVERVIEW

3.2.1 Improper Handling of Exceptional Conditions CWE-755

A denial-of-service vulnerability exists in the affected products. The vulnerability could allow a remote, non-privileged user to send malicious requests resulting in a major nonrecoverable fault causing a denial-of-service.

CVE-2025-24478 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-24478. A base score of 7.1 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Rockwell Automation reported this vulnerability to CISA.

4. MITIGATIONS

Rockwell Automation recommends users of the affected software to apply the risk mitigations, if possible.

  • Update to V33.017, V34.014, V35.013, V36.011, or the latest version.
  • Restrict Access to the task object via CIP Security and Hard Run.
  • For information on how to mitigate security risks on industrial automation control systems, Rockwell Automation encourages users to implement our suggested security best practices to minimize the risk of the vulnerability.

Stakeholder-Specific Vulnerability Categorization can be used to generate more environment-specific prioritization.

For more information about this issue, please see the advisory on the Rockwell Automation security page.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 4, 2025: Initial Publication

Western Telematic Inc NPS Series, DSM Series, CPM Series

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 6.0
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Western Telematic Inc
  • Equipment: NPS Series, DSM Series, CPM Series
  • Vulnerability: External Control of File Name or Path

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an authenticated attacker to gain privileged access to files on the device’s filesystem.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Western Telematic Inc products are affected:

  • Network Power Switch (NPS Series): Firmware Version 6.62 and prior
  • Console Server (DSM Series): Firmware Version 6.62 and prior
  • Console Server + PDU Combo Unit (CPM Series): Firmware Version 6.62 and prior

3.2 VULNERABILITY OVERVIEW

3.2.1 External Control of File Name or Path CWE-73

Multiple Western Telematic (WTI) products contain a web interface that is vulnerable to a Local File Inclusion Attack (LFI), where any authenticated user has privileged access to files on the device’s filesystem.

CVE-2025-0630 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2025-0630. A base score of 6.0 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:P/PR:L/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Communications
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

notnotnotveg ([email protected]) reported this vulnerability to CISA.

4. MITIGATIONS

Western Telematic Inc reports this issue was discovered and patched in 2020. Western Telematic Inc recommends users follow best practices and update to the latest version.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • February 4, 2025: Initial Publication