Skip to main content
(844) 422-7000

Author: Admin @CloudCentric

Siemens TIA Administrator

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.5
  • ATTENTION: Low attack complexity
  • Vendor: Siemens
  • Equipment: TIA Administrator
  • Vulnerabilities: Improper Verification of Cryptographic Signature, Improper Access Control

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to escalate privilege or execute arbitrary code during installations.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • TIA Administrator: All versions prior to V3.0.6

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER VERIFICATION OF CRYPTOGRAPHIC SIGNATURE CWE-347

The affected application improperly validates code signing certificates. This could allow an attacker to bypass the check and execute arbitrary code during installations.

CVE-2025-23364 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.2 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2025-23364. A base score of 6.9 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).

3.2.2 IMPROPER ACCESS CONTROL CWE-284

The affected application allows low-privileged users to trigger installations by overwriting cache files and modifying the downloads path. This would allow an attacker to escalate privilege and execute arbitrary code.

CVE-2025-23365 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-23365. A base score of 8.5 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported these vulnerabilities to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-573669 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.

5. UPDATE HISTORY

  • July 10, 2025: Initial Republication of Siemens SSA-573669

Siemens SIMATIC CN 4100

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.1
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SIMATIC CN 4100
  • Vulnerability: Improper Input Validation

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service condition.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • SIMATIC CN 4100: All versions prior to V4.0

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER INPUT VALIDATION CWE-20

The affected application allows to control the device by storing arbitrary files in the SFTP folder of the device. This could allow an attacker to cause a denial-of-service condition.

CVE-2025-40593 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-40593. A base score of 7.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Michael Klassen and Martin Floeck from BASF Security Team reported this vulnerability to Siemens.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-626991 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • July 10, 2025: Initial Republication of Siemens SSA-626991

Siemens TIA Project-Server and TIA Portal

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 5.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: Project-Server and TIA Portal
  • Vulnerability: Unrestricted Upload of File with Dangerous Type

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to cause a denial-of-service condition.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • TIA Project-Server: Versions prior to V2.1.1
  • TIA Project-Server V17: All versions
  • Totally Integrated Automation Portal (TIA Portal) V17: All versions
  • Totally Integrated Automation Portal (TIA Portal) V18: All versions
  • Totally Integrated Automation Portal (TIA Portal) V19: All versions
  • Totally Integrated Automation Portal (TIA Portal) V20: Versions prior to V20 Update 3

3.2 VULNERABILITY OVERVIEW

3.2.1 UNRESTRICTED UPLOAD OF FILE WITH DANGEROUS TYPE CWE-434

The affected application improperly handles uploaded projects in the document root. This could allow an attacker with contributor privileges to cause denial of service by uploading a malicious project.

CVE-2025-27127 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:L).

A CVSS v4 score has also been calculated for CVE-2025-27127. A base score of 5.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has released new versions for several affected products and recommends updating to the latest versions. Siemens is preparing further fix versions and recommends countermeasures for products where fixes are unavailable or not yet available:

  • TIA Project-Server V17, TIA Portal V17, TIA Portal V18: Currently no fix is planned
  • TIA Portal V19: Currently no fix is available
  • TIA Project-Server: Update to V2.1.1 or later version
  • Totally Integrated Automation Portal (TIA Portal) V20: Update to V20 Update 3 or later version

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-460466 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • July 10, 2025: Initial Republication of Siemens SSA-460466

Delta Electronics DTM Soft

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.4
  • ATTENTION: Low attack complexity
  • Vendor: Delta Electronics
  • Equipment: DTM Soft
  • Vulnerability: Deserialization of Untrusted Data

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to encrypt files referencing the application in order to extract information.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Delta Electronics products are affected:

  • DTM Soft: Versions 1.6.0.0 and prior

3.2 VULNERABILITY OVERVIEW

3.2.1 DESERIALIZATION OF UNTRUSTED DATA CWE-502

Delta DTM Soft is vulnerable to a deserialization of untrusted data vulnerability which may allow an attacker to extract information.

CVE-2025-53415 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-53415. A base score of 8.4 has been calculated; the CVSS vector string is (AV:L/AC:L/AT:N/PR:N/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Taiwan

3.4 RESEARCHER

kimiya working with Trend Micro Zero Day Initiative reported this vulnerability to CISA.

4. MITIGATIONS

Delta has released a new version of DTM Soft on their Download Center and recommends users update to the latest version.

For more information, please see Delta Electronics’ advisory Delta-PCSA-2025-00009..

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.

5. UPDATE HISTORY

  • July 10, 2025: Initial Publication

Siemens SIPROTEC 5

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 6.0
  • ATTENTION: Exploitable remotely
  • Vendor: Siemens
  • Equipment: SIPROTEC 5
  • Vulnerability: Use of GET Request Method With Sensitive Query Strings

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to retrieve sensitive session data from browser history, logs, or other storage mechanisms, potentially leading to unauthorized access.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Siemens reports that the following products are affected:

  • SIPROTEC 5 6MD84 (CP300): All versions
  • SIPROTEC 5 7SA86 (CP300): All versions
  • SIPROTEC 5 7SA87 (CP300): All versions
  • SIPROTEC 5 7SD82 (CP100): All versions
  • SIPROTEC 5 7SD82 (CP150): All versions
  • SIPROTEC 5 7SD86 (CP300): All versions
  • SIPROTEC 5 7SD87 (CP300): All versions
  • SIPROTEC 5 7SJ81 (CP100): All versions
  • SIPROTEC 5 7SJ81 (CP150): All versions
  • SIPROTEC 5 7SJ82 (CP100): All versions
  • SIPROTEC 5 7SJ82 (CP150): All versions
  • SIPROTEC 5 6MD85 (CP300): All versions
  • SIPROTEC 5 7SJ85 (CP300): All versions
  • SIPROTEC 5 7SJ86 (CP300): All versions
  • SIPROTEC 5 7SK82 (CP100): All versions
  • SIPROTEC 5 7SK82 (CP150): All versions
  • SIPROTEC 5 7SK85 (CP300): All versions
  • SIPROTEC 5 7SL82 (CP100): All versions
  • SIPROTEC 5 7SL82 (CP150): All versions
  • SIPROTEC 5 7SL86 (CP300): All versions
  • SIPROTEC 5 7SL87 (CP300): All versions
  • SIPROTEC 5 7SS85 (CP300): All versions
  • SIPROTEC 5 6MD86 (CP300): All versions
  • SIPROTEC 5 7ST85 (CP300): All versions
  • SIPROTEC 5 7ST86 (CP300): All versions
  • SIPROTEC 5 7SX82 (CP150): All versions
  • SIPROTEC 5 7SX85 (CP300): All versions
  • SIPROTEC 5 7SY82 (CP150): All versions
  • SIPROTEC 5 7UM85 (CP300): All versions
  • SIPROTEC 5 7UT82 (CP100): All versions
  • SIPROTEC 5 7UT82 (CP150): All versions
  • SIPROTEC 5 7UT85 (CP300): All versions
  • SIPROTEC 5 7UT86 (CP300): All versions
  • SIPROTEC 5 6MD89 (CP300): All versions
  • SIPROTEC 5 7UT87 (CP300): All versions
  • SIPROTEC 5 7VE85 (CP300): All versions
  • SIPROTEC 5 7VK87 (CP300): All versions
  • SIPROTEC 5 7VU85 (CP300): All versions
  • SIPROTEC 5 Compact 7SX800 (CP050): All versions
  • SIPROTEC 5 6MD89 (CP300) V9.6: All versions
  • SIPROTEC 5 6MU85 (CP300): All versions
  • SIPROTEC 5 7KE85 (CP300): All versions
  • SIPROTEC 5 7SA82 (CP100): All versions
  • SIPROTEC 5 7SA82 (CP150): All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 USE OF GET REQUEST METHOD WITH SENSITIVE QUERY STRINGS CWE-598

The affected devices include session identifiers in URL requests for certain functionalities. This could allow an attacker to retrieve sensitive session data from browser history, logs, or other storage mechanisms, potentially leading to unauthorized access.

CVE-2025-40742 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2025-40742. A base score of 6.0 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:H/AT:N/PR:N/UI:P/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy, Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Siemens

3.4 RESEARCHER

Nozomi Networks reported this vulnerability to Siemens.

4. MITIGATIONS

Siemens is preparing fixed versions and recommends countermeasures for products where fixes are unavailable or not yet available.

Operators of critical power systems (e.g., TSOs or DSOs) worldwide are typically required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. Therefore, operators should check whether appropriate resilient protection measures are in place. The risk of cyber incidents affecting the grid’s reliability can thus be minimized by the grid design. Siemens strongly recommends applying the provided security updates using the corresponding tools and documented procedures that accompany the product. If the product supports this capability, an automated method can be used to apply the security updates across multiple product instances. Siemens strongly recommends validating any security update before it is applied and ensuring that trained staff supervise the update process in the target environment. As a general security measure, Siemens strongly recommends protecting network access with appropriate security mechanisms (e.g., firewalls, segmentation, VPN). It is advised that the environment be configured according to Siemens’ operational guidelines to operate the devices in a protected IT environment.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-904646 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability has a high attack complexity.

5. UPDATE HISTORY

  • July 10, 2025: Initial Republication of Siemens SSA-904646

Advantech iView

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 8.7
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Advantech
  • Equipment: iView
  • Vulnerabilities: Cross-site Scripting, SQL Injection, Path Traversal, Argument Injection.

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to disclose sensitive information, achieve remote code execution, or cause service disruptions.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Advantech products are affected:

  • iView: Versions prior to 5.7.05 build 7057

3.2 VULNERABILITY OVERVIEW

3.2.1 Improper Neutralization of Input During Web Page Generation (‘Cross-site Scripting’) CWE-79

A vulnerability exists in Advantech iView versions prior to 5.7.05 build 7057, which could allow a reflected cross-site scripting (XSS) attack. By exploiting this flaw, an attacker could execute unauthorized scripts in the user’s browser, potentially leading to information disclosure or other malicious activities.

CVE-2025-53397 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.4 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:N).

A CVSS v4 score has also been calculated for CVE-2025-53397. A base score of 5.1 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:A/VC:L/VI:L/VA:N/SC:N/SI:N/SA:N).

3.2.2 Improper Neutralization of Input During Web Page Generation (‘Cross-site Scripting’) CWE-79

A vulnerability exists in Advantech iView versions prior to 5.7.05 build 7057, which could allow a reflected cross-site scripting (XSS) attack. By manipulating specific parameters, an attacker could execute unauthorized scripts in the user’s browser, potentially leading to information disclosure or other malicious activities.

CVE-2025-53519 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.4 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:N).

A CVSS v4 score has also been calculated for CVE-2025-53519. A base score of 5.1 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:A/VC:L/VI:L/VA:N/SC:N/SI:N/SA:N).

3.2.3 Improper Neutralization of Input During Web Page Generation (‘Cross-site Scripting’) CWE-79

A vulnerability exists in Advantech iView versions prior to 5.7.05 build 7057, which could allow a reflected cross-site scripting (XSS) attack. By manipulating certain input parameters, an attacker could execute unauthorized scripts in the user’s browser, potentially leading to information disclosure or other malicious activities.

CVE-2025-41442 has been assigned to this vulnerability. A CVSS v3.1 base score of 5.4 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:N).

A CVSS v4 score has also been calculated for CVE-2025-41442. A base score of 5.1 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:A/VC:L/VI:L/VA:N/SC:N/SI:N/SA:N).

3.2.4 Improper Neutralization of Special Elements used in an SQL Command (‘SQL Injection’) CWE-89

A vulnerability exists in Advantech iView that could allow for SQL injection through the CUtils.checkSQLInjection() function. This vulnerability can be exploited by an authenticated attacker with at least user-level privileges, potentially leading to information disclosure or a denial-of-service condition.

CVE-2025-48891 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:L/A:L).

A CVSS v4 score has also been calculated for CVE-2025-48891. A base score of 7.2 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:L/VA:L/SC:N/SI:N/SA:N).

3.2.5 Improper Limitation of a Pathname to a Restricted Directory (‘Path Traversal’) CWE-22

A vulnerability exists in Advantech iView in NetworkServlet.processImportRequest() that could allow for a directory traversal attack. This issue requires an authenticated attacker with at least user-level privileges. A specific parameter is not properly sanitized or normalized, potentially allowing an attacker to determine the existence of arbitrary files on the server.

CVE-2025-46704 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2025-46704. A base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:L/UI:N/VC:L/VI:N/VA:N/SC:N/SI:N/SA:N).

3.2.6 Improper Neutralization of Special Elements used in an SQL Command (‘SQL Injection’) CWE-89

A vulnerability exists in Advantech iView that could allow for SQL injection and remote code execution through NetworkServlet.getNextTrapPage(). This issue requires an authenticated attacker with at least user-level privileges. Certain parameters in this function are not properly sanitized, allowing an attacker to perform SQL injection and potentially execute code in the context of the ‘nt authoritylocal service’ account.

CVE-2025-53475 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-53475. A base score of 8.7 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.7 Improper Neutralization of Special Elements used in an SQL Command (‘SQL Injection’) CWE-89

A vulnerability exists in Advantech iView that could allow SQL injection and remote code execution through NetworkServlet.archiveTrapRange(). This issue requires an authenticated attacker with at least user-level privileges. Certain input parameters are not properly sanitized, allowing an attacker to perform SQL injection and potentially execute code in the context of the ‘nt authoritylocal service’ account.

CVE-2025-52577 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-52577. A base score of 8.7 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.8 Improper Neutralization of Special Elements used in an SQL Command (‘SQL Injection’) CWE-89

A vulnerability exists in Advantech iView that allows for SQL injection and remote code execution through NetworkServlet.archiveTrap(). This issue requires an authenticated attacker with at least user-level privileges. Certain input parameters are not sanitized, allowing an attacker to perform SQL injection and potentially execute code in the context of the ‘nt authoritylocal service’ account.

CVE-2025-53515 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-53515. A base score of 8.7 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.2.9 Improper Neutralization of Argument Delimiters in a Command (‘Argument Injection’) CWE-88

A vulnerability exists in Advantech iView that allows for argument injection in NetworkServlet.backupDatabase(). This issue requires an authenticated attacker with at least user-level privileges. Certain parameters can be used directly in a command without proper sanitization, allowing arbitrary arguments to be injected. This can result in information disclosure, including sensitive database credentials.

CVE-2025-52459 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2025-52459. A base score of 7.1 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.2.10 Improper Neutralization of Argument Delimiters in a Command (‘Argument Injection’) CWE-88

A vulnerability exists in Advantech iView that allows for argument injection in the NetworkServlet.restoreDatabase(). This issue requires an authenticated attacker with at least user-level privileges. An input parameter can be used directly in a command without proper sanitization, allowing arbitrary arguments to be injected. This can result in information disclosure, including sensitive database credentials.

CVE-2025-53509 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has also been calculated for CVE-2025-53509. A base score of 7.1 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:L/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Taiwan

3.4 RESEARCHER

Alex Williams of Converge Technology Solutions reported these vulnerabilities to CISA.

4. MITIGATIONS

Advantech recommends users update to v5.7.05 build 7057.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • July 10, 2025: Initial Publication

KUNBUS RevPi Webstatus

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: KUNBUS
  • Equipment: RevPi Webstatus
  • Vulnerability: Incorrect Implementation of Authentication Algorithm

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow attackers to bypass authentication and gain unauthorized access to the application.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

KUNBUS reports the following products are affected:

  • Revolution Pi Webstatus: Version 2.4.5 and prior
  • Revolution Pi OS Bullseye: 04/2024
  • Revolution Pi OS Bullseye: 09/2023
  • Revolution Pi OS Bullseye: 07/2023
  • Revolution Pi OS Bullseye: 06/2023
  • Revolution Pi OS Bullseye: 02/2024

3.2 VULNERABILITY OVERVIEW

3.2.1 INCORRECT IMPLEMENTATION OF AUTHENTICATION ALGORITHM CWE-303

The Revolution Pi Webstatus application is vulnerable to an authentication bypass. The password check is vulnerable to an implicit type conversion. This results in incorrect authentication if the JSON value TRUE is provided in the password parameter hashcode.

CVE-2025-41646 has been assigned to this vulnerability. A CVSS v3.1 base score of 9.8 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-41646. A base score of 9.3 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Energy, Transportation Systems, Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Ajay Anto reported this vulnerability to KUNBUS PSIRT, who then reported it to CISA.

4. MITIGATIONS

KUNBUS has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • For Revolution Pi Webstatus Version 2.4.5 and prior: Install the updated package Version 2.4.6 either using apt-get update && apt-get upgrade or download it manually and install via dpkg.

For more information, see the associated KUNBUS PSIRT security advisory, Kunbus-2025-0000003 URL generated by system.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • July 10, 2025: Initial Republication of KUNBUS PSIRT Kunbus-2025-0000003

End-of-Train and Head-of-Train Remote Linking Protocol

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.2
  • ATTENTION: Low attack complexity
  • Standard: End-of-Train and Head-of-Train remote linking protocol
  • Equipment: End-of-Train and Head-of-Train devices
  • Vulnerability: Weak Authentication

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to send their own brake control commands to the end-of-train device, causing a sudden stoppage of the train which may lead to a disruption of operations, or induce brake failure.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following version of End-of-Train and Head-of-Train remote linking protocol is affected:

  • End-of-Train and Head-of-Train remote linking protocol: All versions

3.2 VULNERABILITY OVERVIEW

3.2.1 WEAK AUTHENTICATION CWE-1390

The protocol used for remote linking over RF for End-of-Train and Head-of-Train (also known as a FRED) relies on a BCH checksum for packet creation. It is possible to create these EoT and HoT packets with a software defined radio and issue brake control commands to the EoT device, disrupting operations or potentially overwhelming the brake systems.

CVE-2025-1727 has been assigned to this vulnerability. A CVSS v3 base score of 8.1 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:C/C:L/I:H/A:H).

A CVSS v4 score has also been calculated for CVE-2025-1727. A base score of 7.2 has been calculated; the CVSS vector string is (AV:A/AC:L/AT:N/PR:N/UI:N/VC:L/VI:H/VA:H/SC:N/SI:H/SA:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Transportation Systems
  • COUNTRIES/AREAS DEPLOYED: United States
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Neil Smith and Eric Reuter reported this vulnerability to CISA.

4. MITIGATIONS

The Association of American Railroads (AAR) is pursuing new equipment and protocols which should replace traditional End-of-Train and Head-of-Train devices. The standards committees involved in these updates are aware of the vulnerability and are investigating mitigating solutions.

The AAR Railroad Electronics Standards Committee (RESC) maintains this protocol which is used by multiple manufacturers across the industry, including Hitachi Rail STS USA, Wabtec, Siemens, and others. Users of EoT/HoT devices are recommended to contact their own device manufacturers with questions.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.

5. UPDATE HISTORY

  • June 10, 2025: Initial Publication

Emerson ValveLink Products

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 9.3
  • ATTENTION: Exploitable remotely/Low attack complexity
  • Vendor: Emerson
  • Equipment: ValveLink Products
  • Vulnerabilities: Cleartext Storage of Sensitive Information in Memory, Protection Mechanism Failure, Uncontrolled Search Path Element, Improper Input Validation

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker with access to the system to read sensitive information stored in cleartext, tamper with parameters, and run un-authorized code.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following ValveLink products are affected:

  • ValveLink SOLO: All versions prior to ValveLink 14.0
  • ValveLink DTM: All versions prior to ValveLink 14.0
  • ValveLink PRM: All versions prior to ValveLink 14.0
  • ValveLink SNAP-ON: All versions prior to ValveLink 14.0

3.2 VULNERABILITY OVERVIEW

3.2.1 CLEARTEXT STORAGE OF SENSITIVE INFORMATION IN MEMORY CWE-316

The product stores sensitive information in cleartext in memory. The sensitive memory might be saved to disk, stored in a core dump, or remain uncleared if the product crashes, or if the programmer does not properly clear the memory before freeing it.

CVE-2025-52579 has been assigned to this vulnerability. A CVSS v3 base score of 9.4 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:L).

A CVSS v4 score has also been calculated for CVE-2025-52579. A base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:L/SC:N/SI:N/SA:N).

3.2.2 CLEARTEXT STORAGE OF SENSITIVE INFORMATION IN MEMORY CWE-316

The product stores sensitive information in cleartext within a resource that might be accessible to another control sphere.

CVE-2025-50109 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2025-50109. A base score of 8.5 has been calculated; the CVSS vector string is (AV:L/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).

3.2.3 PROTECTION MECHANISM FAILURE CWE-693

The product does not use or incorrectly uses a protection mechanism that provides sufficient defense against directed attacks against the product.

CVE-2025-46358 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2025-46358. A base score of 8.5 has been calculated; the CVSS vector string is (AV:L/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N).

3.2.4 UNCONTROLLED SEARCH PATH ELEMENT CWE-427

The product uses a fixed or controlled search path to find resources, but one or more locations in that path can be under the control of unintended actors.

CVE-2025-48496 has been assigned to this vulnerability. A CVSS v3 base score of 5.1 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-48496. A base score of 5.9 has been calculated; the CVSS vector string is (AV:L/AC:H/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.2.5 IMPROPER INPUT VALIDATION CWE-20

The product receives input or data, but it does not validate or incorrectly validates that the input has the properties that are required to process the data safely and correctly.

CVE-2025-53471 has been assigned to this vulnerability. A CVSS v3 base score of 5.1 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N).

A CVSS v4 score has also been calculated for CVE-2025-53471. A base score of 5.9 has been calculated; the CVSS vector string is (AV:L/AC:H/AT:N/PR:N/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Emerson reported these vulnerabilities to CISA.

4. MITIGATIONS

Emerson recommends users update their Valvelink software to ValveLink 14.0 or later. The upgrade can be downloaded from the Emerson website.

For more information see the associated Emerson security notification.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • July 8, 2025: Initial Publication

Hitachi Energy Relion 670/650 and SAM600-IO Series

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 7.1
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Hitachi Energy
  • Equipment: Relion 670/650 and SAM600-IO series
  • Vulnerability: Improper Check for Unusual or Exceptional Conditions

2. RISK EVALUATION

An authenticated user with file access privilege via FTP access can cause the Relion 670/650 and SAM600-IO series device to reboot due to improper disk space management.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

Hitachi Energy reports that the following products are affected:

  • Hitachi Energy Relion 650: version 1.0.0 up to and not including 2.0.0
  • Hitachi Energy Relion 650: version 2.1.0 up to 2.2.0
  • Hitachi Energy Relion 650: version 2.2.0 up to 2.2.0.13
  • Hitachi Energy Relion 650: version 2.2.1.0 up to and including 2.2.1.8
  • Hitachi Energy Relion 650: version 2.2.4.0 up to and including 2.2.4.5
  • Hitachi Energy Relion 650: version 2.2.5.0 up to and including 2.2.5.7
  • Hitachi Energy Relion 650: version 2.2.6.0 up to and including 2.2.6.3
  • Hitachi Energy Relion 670: version 1.0.0 up to 2.0.0
  • Hitachi Energy Relion 670: version 2.0.0 up to 2.1.0
  • Hitachi Energy Relion 670: version 2.1.0 up to 2.2.0
  • Hitachi Energy Relion 670: version 2.2.0 up to and including 2.2.0.13
  • Hitachi Energy Relion 670: version 2.2.1.0 up to and including 2.2.1.8
  • Hitachi Energy Relion 670: version 2.2.2.0 up to and including 2.2.2.6
  • Hitachi Energy Relion 670: version 2.2.3.0 up to and including 2.2.3.7
  • Hitachi Energy Relion 670: version 2.2.4.0 up to and including 2.2.4.5
  • Hitachi Energy Relion 670: version 2.2.5.0 up to and including 2.2.5.7
  • Hitachi Energy Relion 670: version 2.2.6.0 up to and including 2.2.6.3
  • Hitachi Energy SAM600-IO: version 2.2.1.0 up to and including 2.2.1.6
  • Hitachi Energy SAM600-IO: version 2.2.5.0 up to and including 2.2.5.7

3.2 VULNERABILITY OVERVIEW

3.2.1 IMPROPER CHECK FOR UNUSUAL OR EXCEPTIONAL CONDITIONS CWE-754

An authenticated user with file access privilege via FTP access can cause the Relion 670/650 and SAM600-IO series device to reboot due to improper disk space management.

CVE-2025-1718 has been assigned to this vulnerability. A CVSS v3.1 base score of 6.5 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:N/I:N/A:H).

A CVSS v4 score has also been calculated for CVE-2025-1718. A base score of 7.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Switzerland

3.4 RESEARCHER

Hitachi Energy PSIRT reported this vulnerability to CISA.

4. MITIGATIONS

Hitachi Energy has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • Relion 670 series version 2.2.6 revisions up to 2.2.6.3, Relion 650 series version 2.2.6 revisions up to 2.2.6.3: Update to version 2.2.6.4 (when available) or latest
  • Relion 670 series version 2.2.5 revisions up to 2.2.5.7, Relion 650 series version 2.2.5 revisions up to 2.2.5.7, SAM600-IO series version 2.2.5 revisions up to 2.2.5.7: Update to version 2.2.5.8 or latest
  • Relion 670 series version 2.2.6 revisions up to 2.2.6.3, Relion 650 series version 2.2.6 revisions up to 2.2.6.3, Relion 670 series version 2.2.5 revisions up to 2.2.5.7, Relion 650 series version 2.2.5 revisions up to 2.2.5.7, SAM600-IO series version 2.2.5 revisions up to 2.2.5.7: Upgrade to version 2.2.7
  • All affected products: Apply general mitigation factors

For more information see the associated Hitachi Energy PSIRT security advisory 8DBD000174 Cybersecurity Advisory – Reboot Vulnerability in Hitachi Energy Relion 670/650 and SAM600-IO series products.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • July 03, 2025: Initial Republication of Hitachi Energy Advisory 8DBD000174